UniPi Extension xS10 is an extension module for UniPi Neuron and UniPi Axon programmable logic controllers. The module allows for a quick extension of automation networks by additional I/Os. The xS10 model combines digital inputs and relay outputs.
The product does not contain a computing module and cannot be used separately.
The UniPi Extension line of extension modules was designed as a quick and inexpensive way to extend the automation networks by additional inputs/outputs without the need to purchase another PLC. Modules are not equipped with a computing module, which is replaced by an additional I/O board. Computing module is represented by a master PLC to which the module is connected via RS485 serial interface.
The xS10 variant is the basic extension module version, combining a set of digital inputs and relay outputs. That makes the xS10 a suitable choice for switching of various two-state devices or external relays based on data from motion sensors, switches or other digital devices.
Features
Digital inputs | 16 | Common features RS485 serial interface (Modbus RTU) Aluminium chassis (IP20) Power supply: 24V DC, 0.63/1.5A |
Relay outputs | 8 | |
RS485 serial interface | 1 |
Inputs & outputs description
Digital inputs (DI) are designed to read binary logic states represented by direct voltage levels. That makes them suitable for reading data from various binary sensors and devices such as switches (on/off), motion sensors (movement detected/not detected), liquid level sensors (full tank/empty tank) etc.
Relay outputs (RO) are primarily used for switching two-state devices with higher current draw such as lightbulbs, thermoelectric valve drives, water heaters, pumps etc.
Communication interfaces
Extension modules communicate through the RS485 interface (Modbus protocol). Connection manual for extension modules can be found on this link
Additional functionality
Along with standard I/O functionality, the module offers several functions to enhance the module's performance and to allow it to react to critical events.
Digital inputs feature Direct Switch functions allowing for connecting digital inputs with relay outputs. Direct Switch can be configured for one of three modes: Copy (switching output by active input), Invert (output is switched by inactive input) and Toggle (output is switched by each input change). Direct Switch is independent of the control software and is thus suitable for applications demanding a lowest possible response time (such as lighting control).
The default setting is a function allowing each processor to save its default configuration. This configuration is loaded after every device reboot triggered either by a manual restart or by a power outage.
MasterWatchdog feature monitors the communication between CPU and me/O board processors. If no exchange occurs within a pre-set timeframe, the MasterWatchdog automatically resets the device and me/O modules back into default settings.
I/O boards of the module feature their control processor, which retains the basic I/O functionality in the case of PLC downtime or connection failure.
Device addressing and DIP switch setting
Addressing the extension module can be done either via control software running on the remote master control unit or can be set manually via the integrated DIP switch. The DIP switch allows the user to set up to 4 bits of address and is evaluated in preference to software settings. If the address on DIP switch is set to “0000”, all DIP switch settings are ignored and the software settings take priority.
Package contents
- extension module
- removable screw terminals
- DIN rail holder (35 mm)
- 2× DIN rail holder mounting screws
- 1× grounding screw
Technical Parameter
Digital inputs | 16 |
Relay outputs | 8 |
RS485 interface | Yes |
Power | 24 V DC |
Dimensions | 90 mm × 70 mm × 60 mm |
Weigth | 310 g |